Products details
GIS circuit breaker ’s motor-operated mechanism MKDJ-013
    Publish time 2019-02-06 20:11    
GIS circuit breaker ’s motor-operated mechanism MKDJ-013
GIS circuit breaker ’s motor-operated mechanism MKDJ-013

Technical parameter

1. Matching with ABB’s GIS circuit breaker and our company’s.

2. output and manually operation share the same shaft. Output torque 80N·m. Output angle±95°

3. exact open position orientation. Motor’s rated voltage is optional from AC/DC,220/110/48/24, motor’s power is 65W.

Matters need attention during operating environment

1.altitude not over 2000m, earthquake magnitude not over 8 degree

2.air temperature lower than +40℃,but not lower than -30℃. Relative temperature daily average not over 95%,  month average not over 90%.

3.the installation site with frequent serious vibration, water vapour, gas, chemical corrosive deposit, salt mist, dust, fire and explosion hazard ,

which evidently affect mechanism’s performance, is not applicable.

Tel: 0086-574-88431113

Fax: 0086-574-88478873

Email: info@macwey.com